Summary Page
| Home Analysis Report | |
| Client(s): | John Doe |
| Property address: | 123 45th Ave Anytown, MN |
| Inspection date: | Monday, June 06, 2005 |
Thank
you for choosing me to be your Home Inspector. I am uniquely capable to acquaint
you with the intricacies of your new home, as I have over two decades of experience
in residential property maintenance and repair.
Additionally, I am nationally
certified to perform inspections by NACHI (the National Association of Certified
Home Inspectors).
As a member of the National Association of Certified
Home Inspectors, it is my fullest intention to provide you with an honest and
concise report. Your presence during the inspection process will provide you with
an introduction to the functionality and safety of your new investment, as I point
out both the areas of concern and the positive aspects of your new home.
I
thank you for the opportunity to serve you!
Robert J Anderson
![]() | Safety | Poses a risk of injury or death |
![]() | Major defect | Correction likely involves a significant expense |
![]() | Repair/Replace | Recommend repairing or replacing |
![]() | Repair/Maintain | Recommend repair and/or maintenance |
![]() | Minor defect | Correction likely involves only a minor expense |
![]() | Maintain | Recommend ongoing maintenance |
![]() | Evaluate | Recommend evaluation by a specialist |
![]() | Monitor | Recommend monitoring in the future |
![]() | Comment | For your information |


- One or
more ground fault circuit interrupter (GFCI) receptacles didn't trip with the
inspector's test instrument. Recommend having a qualified, licensed electrician
evaluate and repair or replace receptacles or the wiring to the receptacles as
necessary.


- The perimeter
grading slopes towards the structure in one or more areas. This can result in
water accumulating around the structure's foundation, or in basements and crawl
spaces if they exist. Accumulated water is a conducive condition to wood destroying
insects and organisms. Wet soil may also cause the foundation to settle and possibly
fail over time. Recommend grading soil so it slopes down and away from the structure
with a slope of at least 5% (10% or better is optimal) for at least 6 feet.

- Recommend cleaning
deck and treating with a waterproof sealant claiming to waterproof, block ultraviolet
light, and stop mildew. Consumer Reports recommends these products: 

- Insulation exposed
in this area. This area needs to be sealed in some way as to prevent access by
any rodents or insects to the attic area. 
- The exterior siding
in some areas is failing. Recommend having a qualified contractor evaluate and
repair these areas. 
- One or more downspouts
have no extensions, or have extensions that are ineffective. This can result in
water accumulating around the structure's foundation, or in basements and crawl
spaces if they exist. Accumulated water is a conducive condition to wood destroying
insects and organisms, and may also cause the foundation to settle and possibly
fail over time. Recommend making repairs as necessary such as repairing or installing
splash blocks or tie-ins to underground drain lines so rain water is carried at
least several feet away from the structure to soil that slopes down and away from
the structure.
- One or more gutters
are missing. This can result in water accumulating around the structure's foundation,
or in basements and crawl spaces if they exist. Accumulated water is a conducive
condition to wood destroying insects and organisms, and may also cause the foundation
to settle and possibly fail over time. Recommend having a qualified contractor
install gutters and downspouts where missing. Also recommend installing extensions
such as splashblocks or tie-ins to underground drain lines where necessary to
carry rain water away from the house.
- The facia trim
has begun to pull away from structure in some areas. Recommend evaluating and
repairing any loose facia found around entire structure.
- Soil is in contact
with or less than 6" from siding and/or trim/windows. This is a conducive condition
for wood destroying insects and organisms,also possible area for water infiltration
and decaying wood and trim because of said clearance.
- Wood trim around
first floor window on south side of structure has decayed and is in need of replacement.


- Vegetation (trees,
shrubs and/or vines) are in contact with the structure's exterior. This is a conducive
condition for wood destroying insects and organisms. Vegetation can serve as a
conduit for insects and may retain moisture against the exterior after it rains.
Recommend pruning or removing vegetation as necessary so there's at least a one
foot gap between all vegetation and the structure's exterior.
- The finish on the deck is worn and/or deteriorated. Recommend cleaning and
repainting deck.
- One or more wooden
deck support posts are in contact with soil. This is a conducive condition for
wood destroying insects and organisms. However no damage from wood destroying
insects or organisms was found. It's recommended that there be at least 6" of
space between any wood and the soil below, even if the wood is treated. If possible,
recommend grading soil so a 6" distance to the soil below is maintained. Otherwise
recommend installing borate based Impel rods to prevent rot. 
- Vegetation (trees,
shrubs and/or vines) are in contact with the structure's exterior. This is a conducive
condition for wood destroying insects and organisms. Vegitation can serve as a
conduit for insects and may retain moisture against the exterior after it rains.
Recommend pruning or removing vegitation as necessary so there's at least a one
foot gap between all vegitation and the structure's exterior.
- Overhead door
is in need of adjusting or greese as the door is binding when lifted. 


- When the
composition shingles were installed a drip molding was not installed first. This
drip edge is installed to overhang the facia by 1/2 inch to prevent water from
running down face of facia. Also this drip allows shingles to overhang facia and
also prevent water from siphoning up and under shingles. Also many areas along
the roof edge the shingles were cut short of facia allowing water infiltration
to roof sheathing and possibly to other surrounding wood framing, this was evident
along the roof edge above west entrance where sheathing under shingles has decayed.
Many areas along roof perimeter also show evidence of the same condition. This
is a major concern as water infiltrating in these areas has already caused damage
and will only worsen with time. Recommend evaluation by a licensed roofing contractor
who can recommend what repairs will need to be done to repair this problem.
- Trees are overhanging
roof and are within 10 feet of roof vertically. This is a conducive condition
for wood destroying insects and organisms since organic debris is more likely
to accumulate on the roof surface. Accumulated debris may cause water to enter
gaps in the roof surface and leak into attic and/or interior spaces. Recommend
pruning trees so they're at least 10 feet above roof, or don't overhang the roof.
- Nail
head protruding under shingles
- Moss is growing on the roof. This is a conducive condition for wood destroying
insects and organisms which can lead to the premature failure of the roof and
subsequent leaks. Recommend treating moss during its growing season (wet months)
with a moss killer. For information on various moss treatment products and their
pros and cons, visit http://bryophytes.science.oregonstate.edu/page24.htm 
- No
smoke detectors are visible. Recommend installing smoke detectors as necessary
so a functioning one exists in each hallway leading to bedrooms, and in each bedroom.
For more information on smoke detectors visit http://www.cpsc.gov/cpscpub/pubs/5077.html
- Exposed
wiring exists in the main service panel due to covers missing from open circuit
breaker slots. Recommend installing covers in open slots. (RED ARROW) 
- Legend for overcurrent
protection devices (breakers or fuses) in the main service panel is missing, unreadable
or incomplete. Recommend installing, updating or correcting the legend as necessary
so it's accurate. (GREEN ARROW) 
- The
estimated useful life for water heaters is 8 to 12 years. This water heater appears
to be approaching this age. Recommend budgeting for a replacement in the near
future. 
- The condensing
line from the furnace should be looked at by the HVAC technician when furnace
is serviced. This line is extremely long and is being pumped straight up. This
may cause problems in the future if pump in system should fail.
- Recommend
that this system be inspected, cleaned, serviced and repaired if necessary by
a qualified heating and cooling technician now and annually in the future.
- Everything appeared
to be in serviceable condition. Ventilation was good. There was some evidence
of past bee infestation. Being that some members of the family are allergic to
bees caution should be taken whenever attic is entered as to not threaten these
family members to possible exposure. 

- Water pressure
is below 40 psi, but the flow appeared to be adequate. 40-80 psi is considered
to be the normal range for water pressure in a home. The inspector performed a
"functional flow test" during the inspection, where multiple fixtures are run
simultaneously, and found there to be adequate flow. For example, the shower flow
didn't decrease significantly when the toilet was flushed.
- Recommend
having septic tank inspected. Recommend pumping tank if last pumped more than
3 years ago.
- Laundry sink
isn't anchored to wall or floor. Recommend having a qualified contractor securely
anchor sink to wall and/or floor to prevent damage to water supply and/or drainage
pipes and causing leaks. 

- No ground
fault circuit interrupter (GFCI) protection device is visible for the sump pump
electric supply. Recommend having a qualified, licensed electrician determine
if a GFCI protection device (receptacle or circuit breaker) exists for the sump
pump and install one if missing to reduce the danger of electric shock.

- Cover
plate(s) are missing from one or more electric receptacle boxes. They are intended
to contain fire and prevent electric shock from exposed wires. This is a safety
hazard and poses a risk of both fire and shock. Recommend installing cover plates
over receptacle boxes where missing.
- The weatherstrip
around one or more exterior entry doors is damaged and/or deteriorated. Recommend
replacing weatherstripping at entry door(s) where necessary. 
- Recommend having
the well water tested for bacteria by a qualified lab. 
- This
well pump has exceeded its estimated useful life of 20 years. The clients should
be aware that this pump may need replacing at any time.
- No GFCI outlets
present in sink area. Recommend having licensed eletricion istall as needed.
- Insulation was
found under kitchen sink. Unable to determine if there was past freezing problems
in this area. Suggest asking previous owner reason for insulation and monitor
to determine if this is a problem area.
- Extension cords
are being used as permanent wiring in one or more areas. They should only be used
for portable equipment on a temporary basis. Using extension cords as permanent
wiring poses a fire and shock hazard, and is an indication that wiring is not
adequate and should be updated. Recommend either removing extension cords or having
a qualified, licensed electrician evaluate and make modification as necessary.
For example, install additional circuits and/or electric outlets.
- Ceiling fan in
this and other bedrooms in upstairs are very low due to low ceiling height. These
fans could cause bodily harm to anybody who may come into contact with them. May
consider removing fans to prevent any possible injury. 

- 2-pronged
receptacles rather than 3-pronged, grounded receptacles are installed in one or
more interior rooms. This limits the ability to use appliances that require a
ground (computers and some other electronic appliances) in these areas. If client
intends to operate electronic devices requiring a ground, then recommend having
a qualified electrian evaluate and install grounded receptacles where necessary
and as per the current National Electric Code. 
- This home was built
before 1978, when laws were enacted in the US preventing the use of lead paint
in residential structures. Lead paint may be present, and is a known safety hazard,
especially to children but also to adults. It may cause brain damage and retarded
mental and physical development, among other things. The paint found in and around
this structure appeared to be intact and and most likely encapsulated by more
recent layers of paint that's not lead-based. However, recommend following precautions
as described in the following links to Consumer Products Safety Commission website
articles regarding possible lead paint.
- Walking on some
sections of the floor results in squeaking or creaking noises. This is usually
the result of substandard construction practices where the subfloor decking isn't
adequately fastened (insufficient glue) to the framing below. In most cases, this
is an annoyance only rather than a structural problem. Various solutions such
as Squeeeeek No More and
Counter Snap fasteners exist to correct this. Repairs to eliminate the squeaks
or creaks may be more or less difficult depending on there being finished hardwood
floors, carpeting over the subfloor, and/or clear access to the underside of the
subfloor. Recommend having a qualified contractor evaluate and repair as necessary.
- One or more
doors don't latch when closed. Recommend making repairs as necessary such as adjusting
latch plates or lockset mechanisms.
- One or more
bathrooms with a shower don't have an exhaust fan installed. Even if a window
that opens exists, it may not provide adequate ventilation, especially during
cold weather when the window is less likely to be opened. Recommend having a qualified
contractor install an exhaust fan, duct and vent cap as per standard building
practices in bathrooms with showers where missing.
- No exhaust fan
is installed in the laundry room. This can lead to excessive accumulation of moisture.
Recommend having a qualified contractor install an exhaust fan with a timer, duct
and vent cap as per standard building practices in the laundry room.